BACKFLOW ON FIRE LINES
By the Ironsmith Fire Engineering Team · Memphis, Shelby County
Backflow preventer testing on a fire line means two different tests under two different rulebooks. The water utility requires a certified tester to prove the check valves hold, so sprinkler water can’t flow back into the public supply. NFPA 25 requires a yearly forward flow test to prove the same assembly lets enough water through to fight a fire. Passing one doesn’t count as passing the other.
Quick facts
- Every Memphis fire line needs one. MLGW treats every fire protection system as a cross-connection risk, because the water in it sits stagnant.
- Your system class picks the device. MLGW allows a double check assembly on Class 1 to 3 fire systems. Class 4 to 6 systems need a reduced pressure assembly.
- The utility test looks backward. A certified tester confirms the checks hold against reverse flow.
- NFPA 25 looks forward. Once a year, the assembly has to pass at least the sprinkler system’s demand.
- Different rules, maybe different people. MLGW requires a Tennessee certified tester it has approved. NFPA 25 calls for a qualified person.
- Ignore it and MLGW can shut off the water. On a fire line, the utility contacts the fire department first.
Backflow preventer testing: two tests, two rulebooks
Here’s how most owners get caught. A tester shows up, hooks a gauge to the backflow preventer, and hands over a passing report. The owner files it and figures the backflow is handled.
Half of it is. That report satisfies the water utility. It doesn’t satisfy NFPA 25, which needs its own test with water actually flowing through the assembly. Older editions of NFPA 25 had their own reverse flow test too, but the 2011 edition dropped it and left that job to local plumbing and utility rules. So now there are two rulebooks, and each one only covers its own test.
Why your fire line has a backflow preventer
Water in sprinkler pipe can sit for years. Some systems also carry antifreeze or other additives, or connect to a second water source. If pressure in the public main drops, that water could siphon back into the drinking supply.
MLGW’s cross connection control program requires an approved double check valve assembly or reduced pressure assembly on every main line connection to a fire protection system.
Double check, detector check or reduced pressure
- Double check valve assembly (DCVA). Two check valves in series. For non-health hazards.
- Double check detector assembly (DCDA). A double check with a metered bypass that catches low flows, such as leaks or unauthorized water use. Built mainly for fire lines.
- Reduced pressure assembly (RP or RPDA). Two checks plus a relief valve that dumps water if the checks leak. Rated for health hazards.
MLGW sorts fire systems into Classes 1 through 6. Classes 1 to 3 may use a double check. Classes 4 to 6, which include systems with auxiliary water supplies, additives or combined industrial and fire use, need a reduced pressure assembly.
Rulebook 1: MLGW and the State of Tennessee
Tennessee requires every community water system to run a cross-connection control program, under rules from the Department of Environment and Conservation. In Memphis, that’s MLGW.
How often
MLGW requires every backflow assembly on a fire line to be tested at least once a year, and its cross connection manual sets a shorter window for double check assemblies. Call MLGW’s cross connection office at 901-528-7757 to confirm the schedule for yours.
Assemblies also need testing right after installation, after any disassembly, and any time they show signs of trouble.
Who can test
The tester needs a Tennessee Certificate of Competency, issued through TDEC’s Fleming Training Center and renewed every three years, and MLGW’s approval. MLGW won’t accept reports from testers who skipped its required annual tester meeting. Reports go on an MLGW-approved form showing every test step and a pass or fail result. As the owner, it’s on you to make sure MLGW receives it.
When it fails
MLGW gives up to 90 days to repair a failed assembly, or 14 days at most on high-hazard premises. A licensed plumber with a permit does the repair, then the assembly is retested. Skip it and MLGW can shut off service. Before it shuts off a fire line, MLGW contacts the fire department, which may condemn the building.
Rulebook 2: NFPA 25’s forward flow test
NFPA 25 requires a forward flow test on fire system backflow preventers every year. Water runs through the assembly at no less than the system’s demand, including hose stream demand where it applies. If the system has no way to flow that much, the test runs at the most flow available.
NFPA 13 calls for a built-in way to run this test, but plenty of older systems were built without one. If yours doesn’t have a test connection, ask how your inspector is handling it.
NFPA 25 also calls for weekly checks on reduced pressure assemblies to make sure the relief port isn’t discharging, and an internal inspection at least every five years. All of it belongs in your NFPA 25 inspection program, along with the rest of your inspection, testing and maintenance.
Why passing one doesn’t pass the other
The utility test is static. With the shutoff valves closed, the tester confirms each check holds a minimum pressure difference. No water flows toward the sprinklers.
The forward flow test checks the opposite direction. It proves the checks open all the way and pass enough water. A check disc that has sat closed for years can stick to its seat and open late or only partway. A static test isn’t built to catch that. A forward flow test is.
What goes wrong on fire line backflow preventers
- Sticky checks. Discs that bond to their seats after sitting, plus corrosion and mineral buildup.
- A leaking relief valve. On a reduced pressure assembly, constant discharge points to a fouled first check, a fouled second check with backpressure, or a fouled relief valve.
- Closed valves. Mistakenly closed control valves are called the number one cause of sprinkler failure, and backflow assemblies have two of them.
- Pressure loss. Every backflow preventer costs some pressure. One industry analysis puts 6-inch double checks at roughly 4 to 7 psi of loss up to 1,000 gpm. Adding or swapping an assembly on an older system can eat the system’s pressure margin, so it needs hydraulic calculations first.
An assembly that can’t pass system demand is a real problem for your sprinkler system, not just a paperwork item.
Put both tests on the calendar
Keep the MLGW test report and the NFPA 25 forward flow results in the same file. Put both dates on the same calendar. Our NFPA 25 inspection schedule lays out every annual and five-year item for your system.
Not sure your forward flow test has ever been done? We’ll check it on your next NFPA 25 inspection.
Frequently asked questions
How often do fire line backflow preventers need to be tested in Memphis?
MLGW requires fire line backflow assemblies to be tested at least once a year, and its manual sets a shorter window for double check assemblies. Confirm your schedule with MLGW. Separately, NFPA 25 requires a forward flow test every year.
What is a forward flow test on a backflow preventer?
A forward flow test runs water through the backflow preventer at no less than the sprinkler system’s demand, including hose streams where required. It proves the check valves open fully and pass enough water to fight a fire. NFPA 25 requires it every year.
Does the annual backflow test satisfy NFPA 25?
No. The utility’s backflow test proves the check valves hold against reverse flow, protecting the drinking water. NFPA 25’s forward flow test proves the assembly passes enough water to the sprinklers. They test opposite directions, and passing one doesn’t count for the other.
Who can test a backflow preventer in Memphis?
MLGW requires a tester with a valid Tennessee Certificate of Competency who is also approved by MLGW and has attended MLGW’s annual tester meeting. Results go on an MLGW-approved form, and the customer is responsible for making sure MLGW receives the report.
What type of backflow preventer does a fire sprinkler system need?
In Memphis, MLGW allows a double check valve assembly on Class 1 to 3 fire systems. Class 4 to 6 systems, such as those with auxiliary water supplies or additives, need a reduced pressure assembly. Double check detector assemblies are common on fire lines because their bypass meter catches low flows.