Holiday building shutdown checklist for fire sprinkler protection in an empty building

The Holiday Shutdown Checklist: Protecting Your Building When Nobody’s There

HOLIDAY SHUTDOWN

By the Ironsmith Fire Engineering Team · Tennessee, Florida, Texas, Arkansas

A building shutdown checklist is the list of steps a facility team runs before a building goes quiet for the holidays: keep the heat on, keep fire protection in service, confirm alarm monitoring and keyholders, and set a schedule for walk-throughs. Fire codes generally require sprinkler and alarm systems in unoccupied buildings to stay in working order. An empty building is exactly where a frozen pipe or a small fire goes unnoticed the longest.

Quick facts

  • Never shut off the sprinkler water. Turn off fixtures you won’t use if you want. Leave the fire supply alone.
  • Keep the heat on. Keep wet pipe areas at 40°F or warmer, and check the cold corners, not just the thermostat.
  • The fire code doesn’t take a holiday. The International Fire Code requires fire alarm, sprinkler and standpipe systems in vacant premises to stay operable, with narrow exceptions.
  • Valves open, and locked open. A closed control valve is a sprinkler system that won’t work.
  • Somebody has to answer the phone. Your alarm company needs current keyholder contacts before you leave.
  • Long closures can change your insurance. Many commercial property policies cut coverage for sprinkler leakage and water damage after 60 consecutive days of vacancy.

Before you lock up: the building shutdown checklist

The best time to plan a holiday shutdown is the week before it starts. Here’s what to run through.

Heat and freeze protection

  • Set thermostats to hold 40°F or warmer anywhere wet sprinkler pipe runs. Some insurers recommend a higher setting, so check your policy.
  • Check the cold spots. Exterior walls, stairwells, mechanical rooms, attics and rarely used restrooms are where pipes freeze first.
  • Drain dry system low points before the break. Our guide to dry system low point drains shows where to find them.
  • Confirm heat trace and pipe insulation are working and intact.
  • Keep the fire pump room heated.

Haven’t done your seasonal prep yet? Start with our fire sprinkler winterization checklist.

Fire protection in service

  • Walk every control valve. Make sure each one is open and sealed or locked.
  • Read the riser gauges and write the numbers down, so you’ll know if they change.
  • Clear open impairments before you leave. If a system has to stay out of service, plan a fire watch for the whole break.
  • Confirm alarm monitoring is active, and update the keyholder list with your monitoring company.
  • Keep fire department connections and hydrants clear of snow, ice and stored material.

Water and power

  • Shut off water to fixtures that won’t be used, like restrooms and break rooms. Never shut off the water supply to your sprinkler system.
  • Know which valve is which. In some buildings the domestic and fire water share a supply. Find out before anyone touches a valve.
  • Don’t cut power to the fire alarm panel, dry system air compressors or heat trace.

Fuel for a fire

  • Clear out clutter, boxes and stored paper, especially near heat sources and electrical rooms.
  • Unplug decorations and portable heaters.
  • Close out any hot work before the break, not during it.

People and plans

  • Name one person who owns the building over the break.
  • Set up keyholders and an emergency plan, and make sure your alarm company has every number.
  • Tell your insurer about any longer closure, and ask how your policy treats it.

During the break: walk-throughs

An empty building can’t report a problem. Schedule walk-throughs, and add extra ones before and after any hard freeze. On each visit, check the temperatures, read the riser gauges, look up at the ceilings for water stains and listen for running water.

If you find a frozen or burst sprinkler pipe, close the main valve before you start thawing. Then call your sprinkler contractor. The system is impaired until it’s repaired, so treat it that way. Our post on frozen sprinkler pipes walks through the first hour.

When you come back

Don’t just open the doors and flip the lights. Walk the building first. Check for leaks, wet ceiling tiles and pooled water. Confirm the fire alarm panel shows normal. Compare the riser gauges with the numbers you wrote down. Turn the domestic water back on one zone at a time and watch for leaks.

Read your vacancy clause

The standard commercial property form most insurers start from limits coverage once a building has been vacant for more than 60 consecutive days. After that point, losses from sprinkler leakage, unless the system was protected against freezing, and from water damage aren’t covered. A holiday break won’t hit 60 days, but a longer closure or a tenant move-out can. Some policies are stricter. Washington’s Supreme Court upheld a policy that cut off water damage coverage the moment the building went vacant. Read your own policy before the break, not after a loss.

Want your sprinkler system checked before the building goes quiet?

Schedule a pre-shutdown inspection

Frequently asked questions

Should I turn off the water to my building over the holidays?

You can shut off water to fixtures that won’t be used, like restrooms and break rooms. Never shut off the water supply to your fire sprinkler system. In buildings where domestic and fire water share a supply, confirm which valve controls what before anyone touches one.

What temperature should a building be kept at during a holiday shutdown?

Keep any area with wet sprinkler pipe at 40°F or warmer. Some insurers recommend a higher setting, so check your policy. Thermostats don’t tell the whole story. Check exterior walls, stairwells and other cold spots where pipes freeze first.

Do fire sprinklers have to stay on in a vacant building?

Generally yes. The International Fire Code requires fire alarm, sprinkler and standpipe systems in vacant premises to stay operable, with narrow exceptions approved by the fire code official. Your local fire code is the final word, so ask your fire marshal before taking any system out of service.

Does a holiday closure affect my property insurance?

A short holiday closure usually won’t trigger a vacancy clause. The standard commercial property form limits coverage after 60 consecutive days of vacancy, including losses from sprinkler leakage and water damage. Some policies are stricter, so read yours and tell your insurer about any longer closure.

What should I check when the building reopens?

Walk the building before full reopening. Look for leaks, wet ceiling tiles and pooled water. Confirm the fire alarm panel is normal and the riser gauges match the readings you took before the break. Turn domestic water back on one zone at a time and watch for leaks.